Lyntec RPCM Manual do Utilizador Página 21

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 20
139-0498-01.21 21
Chapter Five--Control Setup
5. Select a breaker to add to the zone by clicking on the
breaker you want to add. Only motorized breakers
(indicated in green) may be added to zones. (Figure 5-10)
6. Select the position of the breaker in the zone. This set
the order in which they turn on and o . Or in the case
of DMX or sACN, the address order. (Figure 5-11). Note:
DMX and sACN zones default to individual addressing.
If you choose All Available the entire panel or panels
will change to DMX or sACN.
7. For sequenced operation, select a delay time from
the dropdown. Breakers in grouped zones toggle in
25ms intervals. (Figure 5-11) Delay time is the amount
of time after a breaker changes state, before the new
breaker in sequence changes state.
Figure 5-10
Click on the green oval
to add a breaker to a
zone.
Figure 5-11
Click the up/down
arrows to change the
breaker’s position/
address in the zone.
Select a delay time for the
breaker.