139-0600-00 12/1/13RemotePowerControllerfor MobileDistributionInstruction BulletinRetain for future use.LynTec RPCM
139-0498-0110Chapter Four--Wiring10Emergency Shutdown Wiring:To connect your re alarm or emergency management system to the RPCM, follow these steps
139-0498-01.11 11Chapter Four--WiringFigure 4-2: Control WiringInstall and connect a standard Cat. 5e cable from the facility network to the Controll
139-0498-0112Chapter Four--Wiring12INITIAL POWER UP PROCEDUREWith cover o and breakers visible, turn on the panel main breaker and the Controller P
139-0498-01.13 13Chapter Five--Control SetupChapter 5--Control Setup (Web Page)OVERVIEWSTATUS CONTROLSETUPSUPPORTThere are 5 main tabs on your RPC web
139-0498-01.14Chapter Five--Control Setup14SetupSETUP HOMETo set the username and password for your panel, click the Setup tab. The Setup Home tab sho
139-0498-01.15 15Chapter Five--Control SetupNetwork setupFigure 5-2--Network SettingsFigure 5-2 shows the network settings portion of the Network setu
139-0498-01.16Chapter Five--Control Setup16Figure 5-3: Interface optionsNetBios NameThe NetBios name defaults to LynTecRPC. Each master panel in you
139-0498-01.17 17Chapter Five--Control SetupDMXFor DMX operation use the following steps:The RPCM allows up to four di erent sets of DMX starting add
139-0498-01.18Chapter Five--Control Setup18Panel SetupBREAKER SETUPThis section explains how to setup your panel and motorized breakers for remote ope
139-0498-01.19 19Chapter Five--Control SetupZONE SETUPBreakers can be controlled individually or arranged into zones. Breakers in zones can be toggle
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain
139-0498-01.20Chapter Five--Control Setup202. Name the Zone. (Figure 5-7)3. Choose Grouped, Sequenced, DMX or sACN operation. Note: DMX and sACN ma
139-0498-01.21 21Chapter Five--Control Setup5. Select a breaker to add to the zone by clicking on the breaker you want to add. Only motorized breake
139-0498-01.22Chapter Five--Control Setup228. Click the “Close” button when nished to save. Or, click “Remove” to remove the breaker from the zone
139-0498-01.23 23Chapter Five--Control SetupNumbering and addressingThe RPC system allows the user to choose top/bottom panel numbering or left/right
139-0498-01.24Chapter Five--Control Setup24Global Control Preferences The following features can be selected for additional system exibilityFigure 5
139-0498-01.25 25Chapter Five--Control SetupSelecting breakers for Emergency Shutdown, Emergency Lighting or BrownoutFigure 5-17Select breakers to act
139-0498-01.26Chapter Five--Control Setup26Schedule SetupFollow these steps to set a schedule (not applicable for DMX or sACN).1. Enable Schedules in
139-0498-01.27 27Chapter Six--OperationChapter Six: Operating your RPCMFigure 6-1Using the built-in web pageTo operate the RPC using the built in web
139-0498-01.28Appendix A28Appendix A--TCP/IP ProtocolTCP/IP PROTOCOLTCP/IP communications and control via a third party control system is facilitated
139-0498-01.29 29Appendix AEvents include:Event 1 = “All Breakers ON”Event 2 = “All Breakers OFF”Event 3 = “Hurry OFF” zips all breakers o fast.Even
139-0498-01.3 3RPC ControllerTable of ContentsContentsChapter 1--Introduction ...
139-0498-01.30Appendix B--Troubleshooting/FAQ30HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• This equipment must be installed and serviced only
139-0498-01.31 31Appendix B--Troubleshooting/FAQTable C-1: RPC Controller TroubleshootingCondition Possible Causes SolutionsFront Panel LCD and statu
139-0498-01.32Appendix C32Appendix C--RPC System ComponentsThe LynTec system consists of control buses, a panelboard, remotely operated circuit breake
139-0498-01.33 33Appendix CPower Supply The Power Supply connects to a 15A non-motorized breaker and provides 24VDC, 3A power to the RPC controller.F
139-0498-01.34Appendix C34Control Module The RPC Control Module provides control logic for theoperation of a RPC system. The controller uses remotelyo
139-0498-01.35 35Appendix CAuxiliary Power Supply 24 Vdc (200mA maximum Current)Communication Interface RJ-45 (8P8C) TCP/IP/sACN/Web Server/100 Base T
139-0498-01.36Appendix D36Appendix D--RPC System Diagrams and SchematicsNEUTRALCCBBAALR164403910152122272833343918642511121723242930353641142381781319
139-0498-01.37 37Appendix DLOW VOLTAGE SECTIONINTERIOR SPACEREAR PANELFRONT PANEL DISPLAYRPC CONTROLLER24V BUFFERBCPM-APOWER MONITORGN42 POSITIONCIRCU
139-0498-01.4RPC ControllerTable of ContentsAppendix A--TCP/IP Protocol ...
139-0498-01.5 5Chapter One--OverviewThis bulletin explains how to connect and operate the LynTec Remote Power Controller-Mobile Power Distribution Cab
139-0498-01.66Chapter One--OverviewFront Panel Overview Figure 1–1 shows the parts of the RPCM front panel. A brief description of each part follows
139-0498-01.7 7Chapter Two--Safety PrecautionsChapter Two--Safety PrecautionsThis chapter contains important safety precautions that must be followed
139-0498-01.8Chapter Three--Quick Start Guide8Steps Reference1. Connect the RPCM to 120/208V power source See appropriate instruction bulletins.Chapt
139-0498-01.9 9Chapter Four--WiringChapter 4--Wiring1. In this order, connect ground, neutral and phase feeds to rear panel.2. Verify the presence o