Emergency Shutdown Wiring:
To connect your  re alarm or emergency management system
to the RPCM, follow these steps.
1. From the  re alarm unit or latching Emergency Shuto
switch, wire the common to pin 1 and the open circuit to
pin 2 (Figure 4-1).
2. When the Normally Open contacts are closed, all breakers
that have been selected for E. Shuto cycle to OFF.
3. When the contacts are released, the status indicator should
extinguish and, if recovery is checked, all breakers that
were ON when E. Shuto was activated should return to the
ON state.
See Chapter 5 to con gure the software for emergency
shutdown.
Figure 4-1: Override connector
Emergency Lighting Wiring:
To connect your emergency lighting system to the RPCM,
follow these steps.
1. From the  re alarm unit or latching Emergency Lighting
switch, wire the common to pin 1 and the open circuit to
pin 3 (Figure 4-1).
2. When the Normally Open contacts are closed, all breakers
that have been selected for E. Lighting cycle to ON.
3. When the contacts are released, the status indicator should
extinguish and, if recovery is checked, all breakers should
return to their previous state.
See Chapter 5 to con gure the software for emergency
lighting.
To operate Emergency Shutdown and Emergency Lighting
simultaneously, tie pins 2 and 3 together.