Appendix A
42
RPC Contact Closure Wiring Instructions
1
2
3
4
5
6
Left Bus
IN
24V
OUT
Digital I/O
NO
C
NC
+
NO
C
NC
ON
OFF
OFF
LynTec
RPC
Contact
Closure Wiring
Instructions
1
Con rm that RPS (slave) panels are
properly connected to the master as
indicated in the “RPC to RPS Wiring
Instructions” bulletin.
2
Complete all the steps in the “RPC
Quick Start Guide”.
Using a standard LynTec SS-2 Switch
Set with illuminated ON switch. (For
other types of switches, consult CH 4
of the instruction bulletin for wiring
diagrams.)
3
Wire the ON switch to a digital
I/O port on the left edge of the
Controller board as follows:
A. Connect the 24VDC Common
(center terminal of the I/O port)
to the C pin of the ON switch.
B. Connect the Input terminal
(arrow pointing towards header)
to the NO pin of the ON switch.
C. Connect the Output terminal
(arrow pointing away from
header) to the – pin of the ON
switch.
D. Connect a jumper between the
C pin and the + pin of the ON
switch.
4
Wire the OFF switch to a digital
I/O port on the left edge of the
Controller board as follows:
A. Connect the 24VDC Common
terminal to the C pin of the OFF
switch.
B. Connect the Input terminal to the
NO pin of the OFF switch
Note: If using emergency override
features, re alarm contact closures
must be wired into port 1.
5
On the RPC web page, go to
the contact closure page.
(SETUP==> CONTACT CLOSURES)